Active Flow Control Integrated Diffuser for Increased Energy Efficiency in Variable Air Volume Systems

An experimental investigation was performed to study the application of flow control on an HVAC diffuser using synthetic jets distributed evenly along the diffuser edges. The study was conducted on 1:3 scale typical office space (150 ft2) , which included a simulated scale HVAC system supplied by compressed air. Two different jet momentum coefficients were investigated for two inlet flow rates of 40 and 60 CFM. The flow field was measured using hot wire anemometry and Particle Image Velocimetry. Current Variable Air Volume HVAC systems vary the incoming airflow to adjust to changing temperature conditions in the conditioned space. However, when the air flow rate drops below ideal, air distribution becomes inefficient. This study demonstrates the effectiveness of synthetic jets at controlling the incoming airflow and the distribution in the room, showing ability to affect throw coefficient parameters for different flow rates within the test chamber. The use of such devices has the potential to improve air quality and air distribution in building while simultaneously lowering energy demands of HVAC systems. 
Year
2013
Published In
 66th Annual Meeting of the APS Division of Fluid Dynamics, Pittsburg, PA, November 24-26, 2013
Authors
Van Der Schijff, Menicovich, D., Vollen, J., and Amitay, M.
Back to top